              Profile


              MECHANICAL SYSTEMS:
              -----------------------------

              a-Cooling System : Chilled water cooling system Variable primary flow system with single supply and return.

              b-CRAH redundancy: N+1 demand cooling for equipment is 600 w/m.

              c-Fuel Oil: Generator fuel oil storage 72 hours capacity.

              d-BMS: Computerized Building Management System M&E equipment verification and management.

              ELECTRICAL SYSTEMS
              --------------------------
              a-Design load: The electrical connected load is 4.00MVA with a demand load of 2.8.

              b-Transformers: 2 x 1500 KVA and 2 x 1000 KVA .

              c-Generators : 3 x 1600 KVA/1280 KW, 380/220v prime rated diesel generators, design N+1.

              d-Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements.

              e-UPS: Parallel redundant system in N+N configuration, 200KVA modular units with 30 minute battery autonomy at full load.

              f-Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

              g-Security System :Security Analog access control system and IP CCTV integrated with BMS