Data Center Map

                Mobily Tier-2 Unaizah


                » Index » Saudi Arabia » Unaizah » Mobily Tier-2 Unaizah

                Mobily Tier-2 Unaizah is located in the area Unaizah, Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


                Address:
                Mobily
                qassim
                114423 Unaizah
                Unaizah, Saudi Arabia

                » Request quote
                » Visit website

                Click here to find other data centers
                owned and operated by Mobily.


                Profile
                Tenants
                Connectivity
                Request quote
                Office space
                Rack Cabinets
                Dedicated Servers
                Suites
                Footprints
                Virtual Servers
                Cages
                Hosting of individual servers
                Remote Hands

                Profile


                MECHANICAL SYSTEMS:
                -----------------------------

                a-Cooling System : Chilled water cooling system Variable primary flow system with single supply and return.

                b-CRAH redundancy: N+1 demand cooling for equipment is 600 w/m.

                c-Fuel Oil: Generator fuel oil storage 72 hours capacity.

                d-BMS: Computerized Building Management System M&E equipment verification and management.

                ELECTRICAL SYSTEMS
                --------------------------
                a-Design load: The electrical connected load is 4.00MVA with a demand load of 2.8.

                b-Transformers: 2 x 1500 KVA and 2 x 1000 KVA .

                c-Generators : 3 x 1600 KVA/1280 KW, 380/220v prime rated diesel generators, design N+1.

                d-Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements.

                e-UPS: Parallel redundant system in N+N configuration, 200KVA modular units with 30 minute battery autonomy at full load.

                f-Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

                g-Security System :Security Analog access control system and IP CCTV integrated with BMS


                Mobily Tier-2 Unaizah Pricing/Quotes


                If you are interested in receiving a quote for Mobily, please try our free quote service.

                Copyright © Data Center Map - Sitemap
                Your guide to colocation data centers, managed hosting, cloud servers etc.
                波波在线A片免费观看