                Mobily Tier-2 Sulay


                » Index » Saudi Arabia » Riyadh » Mobily Tier-2 Sulay

                Mobily Tier-2 Sulay is located in the area Riyadh (ar-Riya?), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


                Address:
                Mobily
                Riyadh
                11423 Sulay
                Riyadh, Saudi Arabia

                » Request quote
                » Visit website

                Click here to find other data centers
                owned and operated by Mobily.


                Profile
                Tenants
                Connectivity
                Request quote
                Office space
                Rack Cabinets
                Dedicated Servers
                Suites
                Footprints
                Virtual Servers
                Cages
                Hosting of individual servers
                Remote Hands

                Profile


                MECHANICAL SYSTEM
                --------------------------

                a- Cooling System: Refrigerant cooling system.

                b- CRAH redundancy: N+1, Data Center equipment demand cooling load is 1000 W/m2

                c- Fuel Oil: Generator fuel oil storage 48 hours capacity

                d -BMS : Computerized Building Management System M&E equipment verification and management


                ELECTRICAL SYSTEM
                -------------------------
                a- Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.

                b- Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.

                c- Generators: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1

                d- Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel

                e- UPS: parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center

                f- Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time

                g- Security System : IP access control System and Analog CCTV system