                MECHANICAL SYSTEMS
                ---------------------------
                a-Cooling system Chilled water cooling system, dual flow and return with isolating valves at each T section.

                b- CRAH redundancy N+1, Data Center equipment demand cooling load is 1000 W/m2

                c-Fuel Oil Generator fuel oil storage 67 hours capacity at 100% load.

                d-BMS Computerized Building Management System M&E equipment verification and management.

                ELECTRICAL SYSTEMS
                ---------------------------
                a.Design load: The electrical connected load is 10.75 MVA with a demand load of 9 MVA.

                b-Transformers: 8 x 2500 kVA power transformer, 380/220V, 3P, 4W 60 Hz.

                c-Generators: 5 x 2000 kVA/1600 kW Continuous Rated Diesel Generators, Design in N+1.

                d-Paralleling Switch gear: Two set of paralleling switch gear for concurrently maintainable requirements monitored and controlled by two separate Load Shedding Panel.

                e- UPS: parallel redundant system in N+N configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center.

                f- Rectifier System Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

                g-Security System: IP access control system and IP CCTV integrated with BMS for On-Off Status only as per Security Department requirement.