              NEXT GENERATION DATA CENTRE
              544 RUE DE L'INSPECTEUR, MONTREAL

              COMPUTER ROOM SPECIFICATIONS
              Available rooms 7 dedicated data floors plus 1 half floor on ground level each with standard critical power of 1.5MW or 2.0MW per data floor, and high density ready.

              Typical data floors provide 10,000 SF for IT equipment, ~20,000 GSF, and cabinet space 600 standard 24'W x 48"D or 370 standard 32"W x 48"D per data floor. Standard power density of 150 watts per square foot with optional density of 200 watts per square foot

              Structural slab to slab floor heights are 16'6" with loading of over 200 pounds per square foot.

              19,140 SF of office available for lease and ~5,000 SF storage available in basement level

              7x24x365 Security with check points for all access, ballistic glass and walls, electronic access with dual authentication and minimum 1 biometric reader. Video surveillance 7x24x365 of all exterior and interior areas, and minimum 30 days of archive.

              CRITICAL POWER
              Total megawatts 30 MW

              UPS SYSTEMS
              Description - High efficiency static UPS
              Redundancy - N+1 or 2N as required

              GENERATORS
              Description - 2.75 MW diesel generator
              Redundancy - N+1 or 2N as required

              ON SITE FUEL CAPACITY
              5 x 50,000 L + 1 x 30,000 L underground diesel storage
              24 hours minimum run time

              HEAT REJECTION SYSTEMS
              Distributed and N+1 redundant KyotoCooling systems dedicated per data floor.
              Annualized PUE of 1.2 or better unaffected by critical load utilization.

              PDUs
              250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V
              secondary available. 2N redundancy.

              COMMUNICATIONS
              2 separate network points of entry with diverse underground duct banks to local network
              Dedicated diverse conduits and risers to each data floor.
              Carrier neutral facility with multiple carriers.

              FIRE PROTECTION
              Double interlocked pre-action dry type sprinkler system with VESDA throughout building

              DESIGN PUE
              Montreal NGDC is designed to be best in class with an annualized PUE of 1.20 or better regardless of critical load utilization