                NEXT GENERATION DATA CENTRE
                544 RUE DE L'INSPECTEUR, MONTREAL

                COMPUTER ROOM SPECIFICATIONS
                Available rooms 7 dedicated data floors plus 1 half floor on ground level each with standard critical power of 1.5MW or 2.0MW per data floor, and high density ready.

                Typical data floors provide 10,000 SF for IT equipment, ~20,000 GSF, and cabinet space 600 standard 24'W x 48"D or 370 standard 32"W x 48"D per data floor. Standard power density of 150 watts per square foot with optional density of 200 watts per square foot

                Structural slab to slab floor heights are 16'6" with loading of over 200 pounds per square foot.

                19,140 SF of office available for lease and ~5,000 SF storage available in basement level

                7x24x365 Security with check points for all access, ballistic glass and walls, electronic access with dual authentication and minimum 1 biometric reader. Video surveillance 7x24x365 of all exterior and interior areas, and minimum 30 days of archive.

                CRITICAL POWER
                Total megawatts 30 MW

                UPS SYSTEMS
                Description - High efficiency static UPS
                Redundancy - N+1 or 2N as required

                GENERATORS
                Description - 2.75 MW diesel generator
                Redundancy - N+1 or 2N as required

                ON SITE FUEL CAPACITY
                5 x 50,000 L + 1 x 30,000 L underground diesel storage
                24 hours minimum run time

                HEAT REJECTION SYSTEMS
                Distributed and N+1 redundant KyotoCooling systems dedicated per data floor.
                Annualized PUE of 1.2 or better unaffected by critical load utilization.

                PDUs
                250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V
                secondary available. 2N redundancy.

                COMMUNICATIONS
                2 separate network points of entry with diverse underground duct banks to local network
                Dedicated diverse conduits and risers to each data floor.
                Carrier neutral facility with multiple carriers.

                FIRE PROTECTION
                Double interlocked pre-action dry type sprinkler system with VESDA throughout building

                DESIGN PUE
                Montreal NGDC is designed to be best in class with an annualized PUE of 1.20 or better regardless of critical load utilization